American Wire Group - 220 MIL TRXLP 15 KV URD Cable
One Third Neutral
Aluminum Conductor
Search Catalog
By Keyword
By Item #
All Categories
220 MIL TRXLP 15 KV URD Cable
One Third Neutral
Aluminum Conductor
AWG CODE NAME FINDER
Enter code name in the search field to the left for specific product information
All Categories
>
Primary URD Cable
15KV-35KV
>
220 MIL TRXLP 15 KV URD Cable
133% Insulation Level
>
220 MIL TRXLP 15 KV URD Cable
One Third Neutral
Aluminum Conductor
>
View Items
Download PDF
Email This Page
Save To Favorites
220 MIL TRXLP 15 KV URD Cable
One Third Neutral
Aluminum Conductor
Check up to five results to perform an action.
larger image
Applications
For use on single phase and three phase primary underground distribution systems operating at 15kV phase to phase at 100% and 133% insulation level. Suitable for either direct burial or installation in ducts.
Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, TRXLPE (tree-retardant cross-linked polyethylene) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.
Standards
Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.
Results per Page :
25
50
100
200
Results 1 - 10 of 10
1
Item #
Conductor Size AWG
Conductor Stranding
Copper Neutral No. of Wires
Copper Neutral Size AWG
Diameters Conductor
Diameter Over Insulation
Diameter Over Insulation Shield
Diameter Over Neutral Wires
Diameter Over Embedded Jacket
Total w/o Jacket Weight
Total w/ Embedded Jacket Weight
Ampacity 3/C Direct Buried
Ampacity 3/C Triplex Buried
Ampacity 3/C Duct In Air
Conductor
Type
Max. Conductor Temp. (Normal Continuous)
Max. Conductor Temp. (Overload)
Max. Conductor Temp. (Short Circuit)
220-TRXLP-10
1/0
Solid
6
14
0.325 Inches
0.825 Inches
0.905 Inches
1.033 Inches
1.133 Inches
423 Lbs
562 Lbs
230 Amps
165 Amps
145 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-11
1/0
19
6
14
0.362 Inches
0.860 Inches
0.940 Inches
1.068 Inches
1.168 Inches
441 Lbs
580 Lbs
230 Amps
165 Amps
145 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-12
2/0
19
7
14
0.405 Inches
0.905 Inches
0.985 Inches
1.113 Inches
1.213 Inches
490 Lbs
643 Lbs
250 Amps
190 Amps
167 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-13
3/0
19
9
14
0.456 Inches
0.955 Inches
1.035 Inches
1.163 Inches
1.263 Inches
567 Lbs
725 Lbs
280 Amps
215 Amps
189 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-14
4/0
19
11
14
0.512 Inches
1.010 Inches
1.090 Inches
1.218 Inches
1.318 Inches
656 Lbs
842 Lbs
320 Amps
245 Amps
215 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-15
250
37
13
14
0.558 Inches
1.070 Inches
1.190 Inches
1.318 Inches
1.418 Inches
781 Lbs
1013 Lbs
345 Amps
270 Amps
237 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-16
350
37
11
12
0.660 Inches
1.170 Inches
1.290 Inches
1.452 Inches
1.612 Inches
987 Lbs
1266 Lbs
405 Amps
325 Amps
285 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-17
500
37
16
12
0.789 Inches
1.300 Inches
1.420 Inches
1.582 Inches
1.742 Inches
1284 Lbs
1597 Lbs
460 Amps
385 Amps
338 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-18
750
61
15
10
0.968 Inches
1.490 Inches
1.610 Inches
1.814 Inches
1.974 Inches
1774 Lbs
2230 Lbs
515 Amps
475 Amps
417 Amps
Aluminum
90
o
C
130
o
C
250
o
C
220-TRXLP-19
1000
61
20
10
1.117 Inches
1.635 Inches
1.795 Inches
1.999 Inches
2.159 Inches
2301 Lbs
2718 Lbs
565 Amps
540 Amps
475 Amps
Aluminum
90
o
C
130
o
C
250
o
C
Results 1 - 10 of 10
1