Central Office Telephone Cable
EPR/CPE Low Smoke, Conductor - Class I

Check up to five results to perform an action.

Telephone Central Office power cable

larger image

Applications
For use in telephone central office applications, gateways fiber optic amplifiers, wireless towers, data centers, battery back-ups, back-up generators, UPS systems and similar equipment. EPR/CPE Low Smoke 2000 V/108/04101.

Construction
  • UL 44, 2000 V
  • Conductor is tinned annealed copper in accordance with ASTM B-33, B-172, B-173.
  • Insulation is EPR compound per ICEA S-68-51E, UL 44.
  • Jacket is low smoke, heat resisting, flame retardant, oil and sunlight resistant CPE or CP compound.
  • Color of Jacket is black, also available blue, red, green.
  • Maximum conductor operating temperature 90oC wet or dry.
  • Maximum short circuit 250oC

    Standards
  • UL listed as Telephone Central Office Power Cable
  • Flame resistance - cables 1/0 and larger listed and marked FT4/IEEE 1202 and for CT Use.
  • + Low Smoke Characteristics - UL LS FT4/IEEE 1202 meets smoke release and other requirements of vertical cable tray test UL 1685.
  • + MSHA accepted, Approval No. 7K-254020; UL VW-1
  • + Extremely flexible class I stranding used for increased flexibility and easy installation, class H at request.
  • + UL Standard 44. Thermoset Insulated Wires and Cables, Type RHH, RHW-2.

    Notes
  • These ampacities are based on single conductor in free air, 40oC ambient air temperature, 90oC conductor operating temperature.




  • Request InformationCompare Items   Results per Page : 
      Results 1 - 13 of 13 1 

    Item #

    Conductor Size AWG/MCM

    Number of Strands in Conductor

    Nominal Thickness of Insulation (Inches)

    Nominal Thickness of Insulation (mm)

    Nominal
    Jacket
    Thickness
    (Inches)

    Nominal Jacket Thickness (mm)

    Approximate Overall Diameter (Inches)

    Approximate Overall Diameter (mm)

    Approximate
    Weight per 1000 Ft
    (Lbs)

    Ampacity1/C in Free Air, 90°C

    TCI-01-6 6 65 0.062 1.57 0.031 0.08 0.378 9.60 132 96
    TCI-02-4 4 102 0.062 1.57 0.031 0.08 0.452 11.48 197 127
    TCI-03-2 2 163 0.062 1.57 0.031 0.08 0.510 12.95 281 173
    TCI-04-1 1 206 0.078 1.98 0.047 1.19 0.625 15.88 386 200
    TCI-05-1/0 1/0 260 0.078 1.98 0.047 1.19 0.681 17.28 469 237
    TCI-06-2/0 2/0 327 0.078 1.98 0.047 1.19 0.720 18.29 559 273
    TCI-07-3/0 3/0 413 0.078 1.98 0.047 1.19 0.789 20.04 690 319
    TCI-08-4/0 4/0 519 0.078 1.98 0.047 1.19 0.846 21.49 839 369
    TCI-09-250 250 MCM 616 0.094 2.39 0.065 1.65 0.967 24.57 1038 414
    TCI-10-350 350 MCM 859 0.094 2.39 0.065 1.65 1.096 27.84 1386 519
    TCI-11-500 500 MCM 1228 0.109 2.77 0.065 1.65 1.260 32.01 1925 367
    TCI-12-750 750 MCM 1844 0.109 2.77 0.065 1.65 1.470 37.34 2780 805
    TCI-13-1000 1000 MCM 2470 0.109 2.77 0.065 1.65 1.685 42.80 3686 960