    35kV Type MV-105 Power Cable
    345 Mils EPR 100% Insulation
    With PVC Jacket
  • Bare Copper Tape Shield
  • Check up to five results to perform an action.

    MV-105 345 Mils EPR, 35000 Volt Power Cable, Sunlight Resistant, CT Use

    larger image

    Applications
    For installation in tray, trough, conduit, ducts, aerial and direct buried as allowed by the NEC. The cables can be used in main feeder, distribution, and branch circuits for industrial, commercial and electric utility installations. They may operate continuously in wet or dry locations at conductor temperatures not exceeding 105 deg. C, at not more than 140 deg. C. for emergency overload conditions and 250 deg. C during short-circuits. Suitable for systems rated 35 kV, 100% insulation level (grounded systems).

    Construction
    Copper concentrically stranded compressed conductor; triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; bare copper tape shielded; surface printed black PVC jacket.

    Standards
    1) Listed by Underwriters Laboratories as Type MV-90, as per UL Standard 1072. Sizes 4/0 AWG and larger are listed for CT use.
    2) Conforms to NEMA WC74/ICEA S-93-639 Standard for Shielded Power Cables Rated 5,000 – 46,000 Volts for the Transmission and Distribution of Electrical Energy.

    Notes
  • Ampacities are based on the NEC.
  • Cable Tray: Three single cables, installed in uncovered cable tray in accordance with NEC Section 392.13; operating at 105oC conductor, at an ambient temperature of 40oC.
  • Buried Duct: Three cables per duct operating at 105oC conductor, 20oC ground ambient, earth  ρ =  90, 100% load factor.
  • Conduit in Air: Three cables per isolated conduit in air at 40oC; operating at 105oC conductor (NEC Table 310.73).
  • CPE or CSPE Jacket available.




  • Request InformationCompare Items   Results per Page : 
      Results 1 - 9 of 9 1 

    Item #

    Size AWG or KCM

    Stranding

    Minimum Point Insulation

    Minimum Point Jacket

    Diameter Over Insulation

    Diameter Over Insulation Shield

    Diameter Overall

    Net Weight Per 1000 ft.

    Ampacity 1/C in Cable Tray

    Ampacity 1/C Duct Buried

    Ampacity 1/C Conduit In Air

    105-345E1/0 1/0 19 345 mls 70 mls 1.110 Inches 1.200 Inches 1.390 Inches 1180 Lbs N/A 215 Amps 215 Amps
    105-345E2/0 2/0 19 345 mls 70 mls 1.150 Inches 1.250 Inches 1.440 Inches 1300 Lbs N/A 245 Amps 255 Amps
    105-345E3/0 3/0 19 345 mls 70 mls 1.200 Inches 1.290 Inches 1.490 Inches 1460 Lbs N/A 275 Amps 290 Amps
    105-345E4/0 4/0 19 345 mls 70 mls 1.260 Inches 1.340 Inches 1.550 Inches 1650 Lbs 445 Amps 315 Amps 330 Amps
    105-345E250 250 37 345 mls 70 mls 1.330 Inches 1.420 Inches 1.600 Inches 1830 Lbs 495 Amps 345 Amps 365 Amps
    105-345E350 350 37 345 mls 100 mls 1.430 Inches 1.520 Inches 1.780 Inches 2230 Lbs 610 Amps 415 Amps 440 Amps
    105-345E500 500 37 345 mls 100 mls 1.550 Inches 1.660 Inches 1.910 Inches 2930 Lbs 765 Amps 500 Amps 535 Amps
    105-345E750 750 61 345 mls 100 mls 1.740 Inches 1.860 Inches 2.120 Inches 3960 Lbs 990 Amps 610 Amps 655 Amps
    105-345E1000 1000 61 345 mls 100 mls 1.890 Inches 2.020 Inches 2.270 Inches 4920 Lbs 1185 Amps 690 Amps 755 Amps
      Results 1 - 9 of 9 1