American Wire Group - 15kV Type MV-90 Power Cable<br>220 Mils XLP 133% Insulation<br>With PVC Jacket<br><LI>Copper Tape Shielded
 Search Catalog
      GO   
 All Categories    15kV Type MV-90 Power Cable
220 Mils XLP 133% Insulation
With PVC Jacket
  • Copper Tape Shielded
  • AWG CODE NAME FINDER
    Enter code name in the search field to the left for specific product information
    All Categories > Medium Voltage Cable
    MV90 & MV105, Airport Lighting
    5kV - 35kV
     > MV-90 Shielded (XLP) 15kV > 15kV Type MV-90 Power Cable
    220 Mils XLP 133% Insulation
    With PVC Jacket
  • Copper Tape Shielded > View Items 
  •     Download PDF Download PDF     Email Email This Page     Save To Favorites Save To Favorites

    15kV Type MV-90 Power Cable
    220 Mils XLP 133% Insulation
    With PVC Jacket
  • Copper Tape Shielded
  • Check up to five results to perform an action.

    mv90_copper_tape_shield_15000_100_insul.jpg

    larger image

    Applications
    For installation in trough, conduit, ducts, aerial and direct buried as allowed by the NEC. The cables can be used in main feeder, distribution, and branch circuits for industrial, commercial and electric utility installations. They may operate continuously in wet or dry locations at conductor temperatures not exceeding 90 deg. C, at not more than 130 deg. C. for emergency overload conditions and 250 deg. C during short-circuits. Suitable for systems rated 15 kV, 133% insulation level (grounded systems).

    Construction
    Copper concentrically stranded compressed conductor; triple single head extruded conductor shield, XLPE (cross-linked polyethylene) insulation and easy strippable insulation shield, all dry cured; bare copper tape shield; surface printed black PVC jacket.

    Standards
    1) Listed by Underwriters Laboratories as Type MV-90, as per UL Standard 1072.
    2) Conforms to NEMA WC74/ICEA S-93-639 Standard for Shielded Power Cables Rated 5,000 – 46,000 Volts for the Transmission and Distribution of Electrical Energy.

    Notes

    ·  Ampacities are based on the NEC.

    ·  Buried Duct: Three cables per duct operating at 90oC conductor, 20oC ground ambient, earth ρ = 90, 100% load factor.

    ·  Conduit in Air: Three cables per isolated conduit in air at 40oC; operating at 90oC conductor.

  • CPE or CSPE Jacket available.

     





  • Request InformationCompare Items   Results per Page : 
      Results 1 - 10 of 10 1 

    Item #

    Size AWG or KCM

    Stranding

    Insulation Thickness
    (mls)

    Jacket Thickness
    (mls)

    Diameter Over Insulation

    Diameter Over Insulation Shield

    Diameter Overall

    Net Weight Per 1000 ft.

    Ampacity 1/C Conduit In Air

    Ampacity 1/C Duct Buried

    90-152X01W2 2 7 220 70 0.790 Inches 0.860 Inches 1.080 Inches 630 Lbs 155 Amps 150 Amps
    90-152X02W1/0 1/0 19 220 70 0.870 Inches 0.920 Inches 1.140 Inches 760 Lbs 200 Amps 195 Amps
    90-152X03W2/0 2/0 19 220 70 0.910 Inches 0.910 Inches 1.180 Inches 870 Lbs 230 Amps 225 Amps
    90-152X04W3/0 3/0 19 220 70 0.960 Inches 1.010 Inches 1.230 Inches 1010 Lbs 260 Amps 260 Amps
    90-152X05W4/0 4/0 19 220 70 1.020 Inches 1.080 Inches 1.290 Inches 1190 Lbs 295 Amps 295 Amps
    90-152X06W250 250 37 220 70 1.080 Inches 1.140 Inches 1.350 Inches 1360 Lbs 325 Amps 330 Amps
    90-152X07W350 350 37 220 70 1.180 Inches 1.240 Inches 1.470 Inches 1730 Lbs 390 Amps 395 Amps
    90-152X08W500 500 37 220 70 1.310 Inches 1.370 Inches 1.600 Inches 2270 Lbs 465 Amps 480 Amps
    90-152X09W750 750 61 220 100 1.500 Inches 1.560 Inches 1.790 Inches 3260 Lbs 565 Amps 585 Amps
    90-152X10W1000 1000 61 220 100 1.650 Inches 1.730 Inches 2.020 Inches 4160 Lbs 640 Amps 675 Amps
      Results 1 - 10 of 10 1