Quadruplex Service Drop
Aluminum Conductors
AAC Neutral-Messenger
Check up to five results to perform an action.
larger image
Applications
Used to supply 3 phase power, usually from a pole- mounted transformer, to the user's service head where connection to the service entrance cable is made. To be used at voltages of 600 volts or less phase to phase and at conductor temperatures not to exceed 75°C for polyethylene insulated conductors or 90°C for crosslinked polyethylene (XLP) insulated conductors.
Construction
Conductors are concentrically stranded, compressed 1350-H19 aluminum. Insulated with either polyethylene or XLP crosslinked polyethylene. Neutral messengers are concentrically stranded 6201, AAC, or ACSR. One conductor is manufactured with an extruded ridge for phase identification.
Standards
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum conductors, Concentric-Lay-Stranded.
B-232 Aluminum Conductors, Concentric- Lay-Stranded, Coated Steel Reinforced (ACSR).
B-399 Concentric-Lay-Stranded, 6201-T81 Aluminum Alloy Conductors.
B498 Zinc-Coated Steel Core Wire for Aluminum Conductors, Steel Reinforced (ACSR).
Quadruplex Service Drop cable meets or exceeds all applicable requirements of ANSI/ICEA S-76-474.
Note :
Designated sizes are : ACSR 6/1 diameter equivalent and AAC with equivalent resistivity per ASTMB-399 for 6201.Conductor temperature of 90°C for XLR 75°C for Poly; ambient temperatures of 40°C; emissivity 0.9; 2ft./sec/wind in sun. To determine current ampacity by conductor size, please consult The National Electric Code, latest edition.
Results per Page :
25
50
100
200
Results 1 - 8 of 8
1
Item #
Phase Conductor Size AWG
Phase Conductor Stranding
Phase Conductor Insulation Thickness
Bare Neutral Messenger Size AWG
Bare Neutral Messenger Stranding
Bare Neutral messenger Breaking Strength
Weight Per 1000ft - XLP
Weight Per 1000ft - Poly
Ampacity - XLP
Ampacity - Poly
Clydesdale
4
Solid
45 mls
4
7
881 Lbs
208 Lbs
201.8 Lbs
100 Amps
80 Amps
Pinto
4
7/w
45 mls
4
7
881 Lbs
223 Lbs
207.9 Lbs
100 Amps
80 Amps
Mustang
2
7/w
45 mls
2
7
1350 Lbs
333 Lbs
312.6 Lbs
135 Amps
105 Amps
Criollo
1/0
19/w
60 mls
1/0
7
1990 Lbs
529 Lbs
504.5 Lbs
180 Amps
140 Amps
Percheron
2/0
19/w
60 mls
2/0
7
2510 Lbs
649 Lbs
620.5 Lbs
205 Amps
160 Amps
Hanoverian
3/0
19/w
60 mls
3/0
19
3310 Lbs
799 Lbs
765.6 Lbs
235 Amps
185 Amps
Oldenburg
4/0
19/w
60 mls
4/0
19
4020 Lbs
986 Lbs
946.7 Lbs
275 Amps
210 Amps
Lippizaner
336.4
19/w
80 mls
336.4
19
6146 Lbs
1546 Lbs
1519.2 Lbs
370 Amps
280 Amps