American Wire Group - Triplex Conductor 600 V Secondary Type URD Cable - Aluminum Conductor
Search Catalog
By Keyword
By Item #
All Categories
Triplex Conductor 600 V Secondary Type URD Cable - Aluminum Conductor
AWG CODE NAME FINDER
Enter code name in the search field to the left for specific product information
All Categories
>
Secondary Aluminum
600 Volts URD
>
Triplex Conductor Type URD Cable
Aluminum Conductor
>
Triplex Conductor 600 V Secondary Type URD Cable - Aluminum Conductor
>
View Items
Download PDF
Email This Page
Save To Favorites
Triplex Conductor 600 V Secondary Type URD Cable - Aluminum Conductor
Check up to five results to perform an action.
larger image
Applications
Directly buried or installed inducts for 600 volt secondary distribution.
Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yellow striped. Two phase and one neutral conductor twisted together (LH lay) or parallel if so specified. Black neutrals may be specified if desired.
Standards
Secondary UD triplex conductor 600V cable meets or exceeds the following ASTM specifications.
B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
Secondary UD triplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
"USE-2" per UL 854 available upon request.
Options
Cable in Duct (CIC)
Abrasion Resistant
Ampacity
90
o
C conductor temperature, 20
o
C ambient, RHO 50, 100% load factor for three conductor triplex with neutral carrying only unbalanced load. Technical data for cable with solid black neutral is identical to yellow extruded stripe data. All yellow extruded stripe cable is XLP insulation. To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.
Results per Page :
25
50
100
200
Results 1 - 17 of 17
1
Item #
Phase Conductor Size AWG
Phase Conductor Stranding
Phase Conductor Insulation Thickness
Neutral Size AWG
Neutral Stranding
Neutral Insulation Thickness
Single Phase Conductor
Outside Diameter
Weight Per 1000ft
Ampacity Direct Burial
Ampacity In Duct
Erskine
6
7/w
60 mls
6
7/w
60 mls
.299 Inches
.646 Inches
143 Lbs
95 Amps
70 Amps
Vassar
4
7/w
60 mls
4
7/w
60 mls
.345 Inches
.754 Inches
203 Lbs
125 Amps
90 Amps
Stephens
2
7/w
60 mls
4
7/w
60 mls
.403 Inches
.842 Inches
264 Lbs
165 Amps
120 Amps
Ramapo
2
7/w
60 mls
2
7/w
60 mls
.403 Inches
.874 Inches
294 Lbs
165 Amps
120 Amps
Brenau
1/0
19/w
80 mls
2
7/w
60 mls
.522 Inches
1.064 Inches
408 Lbs
215 Amps
160 Amps
Bergen
1/0
19/w
80 mls
1/0
19/w
80 mls
.522 Inches
1.133 Inches
465 Lbs
215 Amps
160 Amps
Converse
2/0
19/w
80 mls
1
19/w
80 mls
.566 Inches
1.174 Inches
502 Lbs
245 Amps
160 Amps
Hunter
2/0
19/w
80 mls
2/0
19/w
80 mls
.566 Inches
1.228 Inches
560 Lbs
245 Amps
180 Amps
Hollins
3/0
19/w
80 mls
1/0
19/w
80 mls
.616 Inches
1.276 Inches
606 Lbs
280 Amps
205 Amps
Rockland
3/0
19/w
80 mls
3/0
19/w
80 mls
.616 Inches
1.336 Inches
678 Lbs
280 Amps
205 Amps
Sweetbriar
4/0
19/w
80 mls
2/0
19/w
80 mls
.672 Inches
1.389 Inches
739 Lbs
315 Amps
240 Amps
Monmouth
4/0
19/w
80 mls
4/0
19/w
80 mls
.672 Inches
1.457 Inches
828 Lbs
315 Amps
240 Amps
Pratt
250
37/w
95 mls
3/0
19/w
80 mls
.748 Inches
1.538 Inches
893 Lbs
345 Amps
265 Amps
Wesleyan
350
37/w
95 mls
4/0
19/w
80 mls
.851 Inches
1.736 Inches
1166 Lbs
415 Amps
320 Amps
Holyoke
500
37/w
95 mls
300
37/w
95 mls
.979 Inches
2.008 Inches
1607 Lbs
495 Amps
395 Amps
Rider
500
37/w
95 mls
350
37/w
95 mls
.979 Inches
2.035 Inches
1663 Lbs
495 Amps
395 Amps
Fairfield
750
61/w
110 mls
500
37/w
95 mls
1.188 Inches
2.0860 Inches
2304 Lbs
615 Amps
525 Amps
Results 1 - 17 of 17
1