American Wire Group - Quadruplex Conductor 600 V Secondary Type URD Cable<br>Aluminum Conductor
 Search Catalog
      GO   
 All Categories    Quadruplex Conductor 600 V Secondary Type URD Cable
Aluminum Conductor
AWG CODE NAME FINDER
Enter code name in the search field to the left for specific product information
All Categories > Secondary Aluminum
600 Volts URD
 > Quadruplex Conductor Type URD
Cable & Mobile Home Feeder
 > Quadruplex Conductor 600 V Secondary Type URD Cable
Aluminum Conductor
 > View Items 

    Download PDF Download PDF     Email Email This Page     Save To Favorites Save To Favorites

Quadruplex Conductor 600 V Secondary Type URD Cable
Aluminum Conductor

Check up to five results to perform an action.

Quadruplex Conductor 600 volt

larger image
Applications
Directly buried or installed in ducts for 600 volt secondary distribution.

Construction
Concentric stranded or compressed 1350-H19 aluminum conductors, crosslinked polyethylene insulation. Insulated conductors surface printed, neutral triple yel low striped. Three phase and one neutral conductor cabled together (LH lay) or parallel if so specified. Black neutrals may be specified is desired.

Standards
Secondary UD quadruplex conductor 600V cable meets or exceeds the following ASTM specifications.
  • B-230 Aluminum Wire, 1350-H19 for Electrical Purposes.
  • B-231 Aluminum 1350 conductors, Concentric-Lay-Stranded.
  • B-786 "19 Wire combination unilay-stranded Aluminum Conductors for subsequent insulation".
  • B-901 "Compressed round stranded Aluminum Conductors using single input wire construction".
  • Secondary UD quadruplex conductor 600V cable meets or exceeds all applicable requirements of ICEA S-105-692.
  • "USE-2" per UL 854 available upon request.

    Options
  • Cable in Duct (CIC)
  • Abrasion Resistant


  • Ampacity
    To determine correct ampacity by conductor size, please consult the National Electric Code, latest edition.




    Request InformationCompare Items   Results per Page : 
      Results 1 - 14 of 14 1 

    Item #

    Phase Conductor Size AWG

    Phase Conductor Stranding

    Phase Conductor Insulation Thickness

    Neutral Size AWG

    Neutral Stranding

    Neutral Insulation Thickness

    Single Phase Conductor

    Outside Diameter

    Weight Per 1000ft

    Ampacity Direct Burial

    Ampacity In Duct

    Tulsa 4 7 60 mls 4 4 60 mls .345 Inches .833 Inches 258 Lbs 119 Amps 85 Amps
    Dyke 2 7 60 mls 4 4 60 mls .403 Inches .938 Inches 346 Lbs 153 Amps 115 Amps
    Wittenberg 2 7 60 mls 2 2 60 mls .403 Inches .973 Inches 375 Lbs 153 Amps 115 Amps
    Notre Dame 1/0 19 80 mls 2 2 60 mls .522 Inches 1.188 Inches 541 Lbs 198 Amps 150 Amps
    Purdue 1/0 19 80 mls 1/0 1/0 80 mls .522 Inches 1.260 Inches 596 Lbs 198 Amps 150 Amps
    Syracuse 2/0 19 80 mls 1 1 80 mls .566 Inches 1.316 Inches 664 Lbs 225 Amps 170 Amps
    Lafayette 2/0 19 80 mls 2/0 2/0 80 mls .566 Inches 1.367 Inches 720 Lbs 225 Amps 170 Amps
    Swarthmore 3/0 19 80 mls 1/0 1/0 80 mls .616 Inches 1.430 Inches 805 Lbs 250 Amps 195 Amps
    Davidson 3/0 19 80 mls 3/0 3/0 80 mls .616 Inches 1.487 Inches 874 Lbs 250 Amps 195 Amps
    Wake Forest 4/0 19 80 mls 2/0 2/0 80 mls .672 Inches 1.560 Inches 979 Lbs 290 Amps 225 Amps
    Earlham 4/0 19 80 mls 4/0 4/0 80 mls .672 Inches 1.623 Inches 1066 Lbs 290 Amps 225 Amps
    Slippery Rock 350 37 95 mls 4/0 4/0 80 mls .851 Inches 1.945 Inches 1544 Lbs 385 Amps 305 Amps
    Wofford 500 37 95 mls 350 350 95 mls .851 Inches 2.348 Inches 2174 Lbs 467 Amps 420 Amps
    Windham 750 61 110 mls 500 500 95 mls .979 Inches 2.850 Inches 2542 Lbs 615 Amps 492 Amps
      Results 1 - 14 of 14 1