American Wire Group - 175 MIL EPR 15 KV URD Cable
Full Neutral
Aluminum Conductor
Search Catalog
By Keyword
By Item #
All Categories
175 MIL EPR 15 KV URD Cable
Full Neutral
Aluminum Conductor
AWG CODE NAME FINDER
Enter code name in the search field to the left for specific product information
All Categories
>
Primary URD Cable
15KV-35KV
>
175 MIL EPR 15 KV URD Cable
100% Insulation Level
>
175 MIL EPR 15 KV URD Cable
Full Neutral
Aluminum Conductor
>
View Items
Download PDF
Email This Page
Save To Favorites
175 MIL EPR 15 KV URD Cable
Full Neutral
Aluminum Conductor
Check up to five results to perform an action.
larger image
Applications
For use on single phase and three phase primary underground distribution systems operating at 15kV phase to phase at 100% insulation level. Suitable for either direct burial or installation in ducts.
Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.
Standards
Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.
Results per Page :
25
50
100
200
Results 1 - 9 of 9
1
Item #
Conductor Size AWG
Conductor Stranding
Copper Neutral No. of Wires
Copper Neutral Size AWG
Diameters Conductor
Diameter Over Insulation
Diameter Over Insulation Shield
Diameter Over Neutral Wires
Diameter Over Embedded Jacket
Total w/o Jacket Weight
Total w/ Embedded Jacket Weight
Ampacity 1/C Direct Buried
Ampacity 1/C Duct Buried
Ampacity 1/C Duct In Air
Conductor
Type
Max. Conductor Temp. (Normal Continuous)
Max. Conductor Temp. (Overload)
Max. Conductor Temp. (Short Circuit)
175-EPR-01
2
Solid
10
14
0.258 Inches
0.670 Inches
0.750 Inches
0.878 Inches
0.978 Inches
451 Lbs
512 Lbs
170 Amps
115 Amps
100 Amps
Aluminum
90
o
C
130
o
C
250
o
C
175-EPR-02
2
7
10
14
0.290 Inches
0.690 Inches
0.750 Inches
0.880 Inches
0.980 Inches
455 Lbs
518 Lbs
170 Amps
115 Amps
100 Amps
Aluminum
90
o
C
130
o
C
250
o
C
175-EPR-03
1
Solid
13
14
0.289 Inches
0.700 Inches
0.780 Inches
0.908 Inches
1.008 Inches
520 Lbs
581 Lbs
195 Amps
140 Amps
123 Amps
Aluminum
90
o
C
130
o
C
250
o
C
175-EPR-04
1
19
13
14
0.330 Inches
0.730 Inches
0.800 Inches
0.930 Inches
1.030 Inches
536 Lbs
600 Lbs
195 Amps
140 Amps
123 Amps
Aluminum
90
o
C
130
o
C
250
o
C
175-EPR-05
1/0
Solid
16
14
0.325 Inches
0.735 Inches
0.815 Inches
0.943 Inches
1.043 Inches
594 Lbs
656 Lbs
230 Amps
155 Amps
135 Amps
Aluminum
90
o
C
130
o
C
250
o
C
175-EPR-06
1/0
19
16
14
0.370 Inches
0.770 Inches
0.840 Inches
0.970 Inches
1.070 Inches
615 Lbs
680 Lbs
230 Amps
155 Amps
135 Amps
Aluminum
90
o
C
130
o
C
250
o
C
175-EPR-07
2/0
19
13
12
0.420 Inches
0.820 Inches
0.880 Inches
1.010 Inches
1.110 Inches
732 Lbs
810 Lbs
270 Amps
185 Amps
162 Amps
Aluminum
90
o
C
130
o
C
250
o
C
175-EPR-08
3/0
19
16
12
0.470 Inches
0.870 Inches
0.930 Inches
1.100 Inches
1.200 Inches
848 Lbs
927 Lbs
295 Amps
210 Amps
184 Amps
Aluminum
90
o
C
130
o
C
250
o
C
175-EPR-09
4/0
19
20
12
0.530 Inches
0.930 Inches
0.990 Inches
1.150 Inches
1.260 Inches
1009 Lbs
1090 Lbs
335 Amps
240 Amps
210 Amps
Aluminum
90
o
C
130
o
C
250
o
C
Results 1 - 9 of 9
1