American Wire Group - 175 MIL EPR 15 KV URD Cable
One Third Neutral
Copper Conductor
Search Catalog
By Keyword
By Item #
All Categories
175 MIL EPR 15 KV URD Cable
One Third Neutral
Copper Conductor
AWG CODE NAME FINDER
Enter code name in the search field to the left for specific product information
All Categories
>
Primary URD Cable
15KV-35KV
>
175 MIL EPR 15 KV URD Cable
100% Insulation Level
>
175 MIL EPR 15 KV URD Cable
One Third Neutral
Copper Conductor
>
View Items
Download PDF
Email This Page
Save To Favorites
175 MIL EPR 15 KV URD Cable
One Third Neutral
Copper Conductor
Check up to five results to perform an action.
larger image
Applications
For use on single phase and three phase primary underground distribution systems operating at 15kV phase to phase at 100% insulation level. Suitable for either direct burial or installation in ducts.
Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.
Standards
Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.
Results per Page :
25
50
100
200
Results 1 - 9 of 9
1
Item #
Conductor Size AWG
Conductor Stranding
Copper Neutral No. of Wires
Copper Neutral Size AWG
Diameters Conductor
Diameter Over Insulation
Diameter Over Insulation Shield
Diameter Over Neutral Wires
Diameter Over Embedded Jacket
Total w/o Jacket Weight
Total w/ Embedded Jacket Weight
Ampacity 3/C Direct Buried
Ampacity 3/C Triplex Buried
Ampacity 3/C Duct In Air
Conductor
Type
Max. Conductor Temp. (Normal Continuous)
Max. Conductor Temp. (Overload)
Max. Conductor Temp. (Short Circuit)
175-EPR-26
1/0
19
9
14
0.370 Inches
0.770 Inches
0.840 Inches
0.970 Inches
1.070 Inches
749 Lbs
814 Lbs
290 Amps
210 Amps
185 Amps
Copper
90
o
C
130
o
C
250
o
C
175-EPR-27
2/0
19
11
14
0.420 Inches
0.820 Inches
0.880 Inches
1.010 Inches
1.110 Inches
891 Lbs
969 Lbs
320 Amps
240 Amps
210 Amps
Copper
90
o
C
130
o
C
250
o
C
175-EPR-28
3/0
19
14
14
0.470 Inches
0.870 Inches
0.930 Inches
1.100 Inches
1.200 Inches
1056 Lbs
1135 Lbs
350 Amps
275 Amps
241 Amps
Copper
90
o
C
130
o
C
250
o
C
175-EPR-29
4/0
19
11
12
0.530 Inches
0.930 Inches
0.990 Inches
1.150 Inches
1.250 Inches
1267 Lbs
1348 Lbs
390 Amps
315 Amps
276 Amps
Copper
90
o
C
130
o
C
250
o
C
175-EPR-30
250
37
13
12
0.570 Inches
0.990 Inches
1.050 Inches
1.190 Inches
1.290 Inches
1487 Lbs
1597 Lbs
415 Amps
340 Amps
298 Amps
Copper
90
o
C
130
o
C
250
o
C
175-EPR-31
350
37
12
10
0.680 Inches
1.090 Inches
1.190 Inches
1.360 Inches
1.460 Inches
2022 Lbs
2164 Lbs
475 Amps
415 Amps
364 Amps
Copper
90
o
C
130
o
C
250
o
C
175-EPR-32
500
37
17
10
0.810 Inches
1.220 Inches
1.330 Inches
1.490 Inches
1.590 Inches
2712 Lbs
2860 Lbs
525 Amps
480 Amps
420 Amps
Copper
90
o
C
130
o
C
250
o
C
175-EPR-33
750
61
25
10
0.990 Inches
1.410 Inches
1.520 Inches
1.720 Inches
1.890 Inches
3873 Lbs
4063 Lbs
560 Amps
530 Amps
465 Amps
Copper
90
o
C
130
o
C
250
o
C
175-EPR-34
1000
61
33
10
1.140 Inches
1.570 Inches
1.710 Inches
1.920 Inches
2.030 Inches
5028 Lbs
5231 Lbs
600 Amps
590 Amps
518 Amps
Copper
90
o
C
130
o
C
250
o
C
Results 1 - 9 of 9