220 MIL EPR 15 KV URD Cable
One Third Neutral
Copper Conductor

Check up to five results to perform an action.

URD Cable

larger image

Applications
For use on single phase and three phase primary underground distribution systems operating at 15kV phase to phase at 100% and 133% insulation level.  Suitable for either direct burial or installation in ducts.

Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
  • Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
  • Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.





  • Request InformationCompare Items   Results per Page : 
      Results 1 - 9 of 9 1 

    Item #

    Conductor Size AWG

    Conductor Stranding

    Copper Neutral No. of Wires

    Copper Neutral Size AWG

    Diameters Conductor

    Diameter Over Insulation

    Diameter Over Insulation Shield

    Diameter Over Neutral Wires

    Diameter Over Embedded Jacket

    Total w/o Jacket Weight

    Total w/ Embedded Jacket Weight

    Ampacity 3/C Direct Buried

    Ampacity 3/C Triplex Buried

    Ampacity 3/C Duct In Air

    Conductor
    Type

    Max. Conductor Temp. (Normal Continuous)

    Max. Conductor Temp. (Overload)

    Max. Conductor Temp. (Short Circuit)

    220-EPR-26 1/0 19 9 14 0.370 Inches 0.870 Inches 0.930 Inches 1.080 Inches 1.181 Inches 825 Lbs 898 Lbs 290 Amps 210 Amps 185 Amps Copper 90 oC 130 oC 250 oC
    220-EPR-27 2/0 19 11 14 0.420 Inches 0.910 Inches 0.980 Inches 1.100 Inches 1.207 Inches 967 Lbs 1054 Lbs 320 Amps 240 Amps 210 Amps Copper 90 oC 130 oC 250 oC
    220-EPR-28 3/0 19 14 14 0.470 Inches 0.960 Inches 1.030 Inches 1.190 Inches 1.291 Inches 1134 Lbs 1223 Lbs 350 Amps 275 Amps 241 Amps Copper 90 oC 130 oC 250 oC
    220-EPR-29 4/0 19 11 12 0.530 Inches 1.020 Inches 1.120 Inches 1.310 Inches 1.410 Inches 1393 Lbs 1486 Lbs 390 Amps 315 Amps 276 Amps Copper 90 oC 130 oC 250 oC
    220-EPR-30 250 37 13 12 0.570 Inches 1.080 Inches 1.180 Inches 1.410 Inches 1.509 Inches 1616 Lbs 1730 Lbs 415 Amps 340 Amps 298 Amps Copper 90 oC 130 oC 250 oC
    220-EPR-31 350 37 12 10 0.680 Inches 1.180 Inches 1.290 Inches 1.490 Inches 1.592 Inches 2130 Lbs 2280 Lbs 475 Amps 415 Amps 364 Amps Copper 90 oC 130 oC 250 oC
    220-EPR-32 500 37 17 10 0.810 Inches 1.310 Inches 1.420 Inches 1.620 Inches 1.786 Inches 2825 Lbs 2985 Lbs 525 Amps 480 Amps 420 Amps Copper 90 oC 130 oC 250 oC
    220-EPR-33 750 61 25 10 0.990 Inches 1.510 Inches 1.610 Inches 1.810 Inches 1.980 Inches 4058 Lbs 4263 Lbs 560 Amps 530 Amps 465 Amps Copper 90 oC 130 oC 250 oC
    220-EPR-34 1000 61 33 10 1.140 Inches 1.660 Inches 1.810 Inches 2.010 Inches 2.175 Inches 5171 Lbs 5386 Lbs 600 Amps 590 Amps 518 Amps Copper 90 oC 130 oC 250 oC