220 MIL EPR 15 KV URD Cable
One Third Neutral
Aluminum Conductor

Check up to five results to perform an action.

URD Cable

larger image

Applications
For use on single phase and three phase primary underground distribution systems operating at 15kV phase to phase at 100% and 133% insulation level.  Suitable for either direct burial or installation in ducts.

Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
  • Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
  • Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.





  • Request InformationCompare Items   Results per Page : 
      Results 1 - 10 of 10 1 

    Item #

    Conductor Size AWG

    Conductor Stranding

    Copper Neutral No. of Wires

    Copper Neutral Size AWG

    Diameters Conductor

    Diameter Over Insulation

    Diameter Over Insulation Shield

    Diameter Over Neutral Wires

    Diameter Over Embedded Jacket

    Total w/o Jacket Weight

    Total w/ Embedded Jacket Weight

    Ampacity 3/C Direct Buried

    Ampacity 3/C Triplex Buried

    Ampacity 3/C Duct In Air

    Conductor
    Type

    Max. Conductor Temp. (Normal Continuous)

    Max. Conductor Temp. (Overload)

    Max. Conductor Temp. (Short Circuit)

    220-EPR-10 1/0 Solid 6 14 0.325 Inches 0.825 Inches 0.905 Inches 1.033 Inches 1.133 Inches 541 Lbs 616 Lbs 230 Amps 165 Amps 145 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-11 1/0 19 6 14 0.370 Inches 0.870 Inches 0.930 Inches 1.060 Inches 1.161 Inches 558 Lbs 631 Lbs 230 Amps 165 Amps 145 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-12 2/0 19 7 14 0.420 Inches 0.910 Inches 0.980 Inches 1.100 Inches 1.207 Inches 628 Lbs 715 Lbs 250 Amps 190 Amps 167 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-13 3/0 19 9 14 0.470 Inches 0.960 Inches 1.030 Inches 1.190 Inches 1.291 Inches 708 Lbs 797 Lbs 280 Amps 215 Amps 189 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-14 4/0 19 11 14 0.530 Inches 1.020 Inches 1.120 Inches 1.270 Inches 1.369 Inches 863 Lbs 956 Lbs 320 Amps 245 Amps 215 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-15 250 37 13 14 0.570 Inches 1.080 Inches 1.180 Inches 1.370 Inches 1.469 Inches 978 Lbs 1092 Lbs 345 Amps 270 Amps 237 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-16 350 37 11 12 0.680 Inches 1.180 Inches 1.290 Inches 1.450 Inches 1.552 Inches 1219 Lbs 1369 Lbs 405 Amps 325 Amps 285 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-17 500 37 16 12 0.810 Inches 1.310 Inches 1.420 Inches 1.580 Inches 1.746 Inches 1555 Lbs 1715 Lbs 460 Amps 385 Amps 338 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-18 750 61 15 10 0.990 Inches 1.510 Inches 1.610 Inches 1.810 Inches 1.980 Inches 2144 Lbs 2349 Lbs 515 Amps 475 Amps 417 Amps Aluminum 90 oC 130 oC 250 oC
    220-EPR-19 1000 61 20 10 1.140 Inches 1.660 Inches 1.810 Inches 2.010 Inches 2.175 Inches 2667 Lbs 2882 Lbs 565 Amps 540 Amps 475 Amps Aluminum 90 oC 130 oC 250 oC