260 MIL EPR 25 KV URD Cable
One Third Neutral
Copper Conductor

Check up to five results to perform an action.

URD Cable

larger image

Applications
For use on single phase and three phase primary underground distribution systems operating at 25kV phase to phase at 100% insulation level.  Suitable for either direct burial or installation in ducts.

Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
  • Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
  • Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.





  • Request InformationCompare Items   Results per Page : 
      Results 1 - 9 of 9 1 

    Item #

    Conductor Size AWG

    Conductor Stranding

    Copper Neutral No. of Wires

    Copper Neutral Size AWG

    Diameters Conductor

    Diameter Over Insulation

    Diameter Over Insulation Shield

    Diameter Over Neutral Wires

    Diameter Over Embedded Jacket

    Total w/o Jacket Weight

    Total w/ Embedded Jacket Weight

    Ampacity 3/C Direct Buried

    Ampacity 3/C Triplex Buried

    Ampacity 3/C Duct In Air

    Conductor
    Type

    Max. Conductor Temp. (Normal Continuous)

    Max. Conductor Temp. (Overload)

    Max. Conductor Temp. (Short Circuit)

    260-EPR-23 1/0 19 9 14 0.370 Inches 0.950 Inches 1.010 Inches 1.140 Inches 1.240 Inches 896 Lbs 996 Lbs 275 Amps 215 Amps 189 Amps Copper 90 oC 130 oC 250 oC
    260-EPR-24 2/0 19 11 14 0.420 Inches 0.990 Inches 1.060 Inches 1.190 Inches 1.290 Inches 1045 Lbs 1148 Lbs 310 Amps 250 Amps 220 Amps Copper 90 oC 130 oC 250 oC
    260-EPR-25 3/0 19 14 14 0.470 Inches 1.040 Inches 1.150 Inches 1.310 Inches 1.410 Inches 1246 Lbs 1353 Lbs 345 Amps 285 Amps 250 Amps Copper 90 oC 130 oC 250 oC
    260-EPR-26 4/0 19 11 12 0.530 Inches 1.100 Inches 1.210 Inches 1.390 Inches 1.490 Inches 1491 Lbs 1634 Lbs 385 Amps 320 Amps 280 Amps Copper 90 oC 130 oC 250 oC
    260-EPR-27 250 37 13 12 0.570 Inches 1.160 Inches 1.260 Inches 1.490 Inches 1.590 Inches 1724 Lbs 1896 Lbs 410 Amps 345 Amps 303 Amps Copper 90 oC 130 oC 250 oC
    260-EPR-28 350 37 12 10 0.680 Inches 1.260 Inches 1.400 Inches 1.570 Inches 1.740 Inches 2239 Lbs 2423 Lbs 460 Amps 405 Amps 355 Amps Copper 90 oC 130 oC 250 oC
    260-EPR-29 500 37 17 10 0.810 Inches 1.400 Inches 1.500 Inches 1.700 Inches 1.870 Inches 2951 Lbs 3185 Lbs 520 Amps 470 Amps 412 Amps Copper 90 oC 130 oC 250 oC
    260-EPR-30 750 61 25 10 0.990 Inches 1.590 Inches 1.730 Inches 1.940 Inches 2.100 Inches 4208 Lbs 4453 Lbs 567 Amps 550 Amps 483 Amps Copper 90 oC 130 oC 250 oC
    260-EPR-31 1000 61 33 10 1.140 Inches 1.740 Inches 1.890 Inches 2.090 Inches 2.260 Inches 5331 Lbs 5331 Lbs 625 Amps 615 Amps 540 Amps Copper 90 oC 130 oC 250 oC