American Wire Group - 260 MIL EPR 25 KV URD Cable<br>Full Neutral<br>Aluminum Conductor
 Search Catalog
      GO   
 All Categories    260 MIL EPR 25 KV URD Cable
Full Neutral
Aluminum Conductor
AWG CODE NAME FINDER
Enter code name in the search field to the left for specific product information
All Categories > 
Primary URD Cable
15KV-35KV
 > 260 MIL EPR 25 KV URD Cable
100% Insulation Level
 > 260 MIL EPR 25 KV URD Cable
Full Neutral
Aluminum Conductor
 > View Items 

    Download PDF Download PDF     Email Email This Page     Save To Favorites Save To Favorites

260 MIL EPR 25 KV URD Cable
Full Neutral
Aluminum Conductor

Check up to five results to perform an action.

URD Cable

larger image

Applications
For use on single phase and three phase primary underground distribution systems operating at 25kV phase to phase at 100% insulation level.  Suitable for either direct burial or installation in ducts.

Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
  • Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
  • Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.





  • Request InformationCompare Items   Results per Page : 
      Results 1 - 7 of 7 1 

    Item #

    Conductor Size AWG

    Conductor Stranding

    Copper Neutral No. of Wires

    Copper Neutral Size AWG

    Diameters Conductor

    Diameter Over Insulation

    Diameter Over Insulation Shield

    Diameter Over Neutral Wires

    Diameter Over Embedded Jacket

    Total w/o Jacket Weight

    Total w/ Embedded Jacket Weight

    Ampacity 1/C Direct Buried

    Ampacity 1/C Duct Buried

    Ampacity 1/C Duct In Air

    Conductor
    Type

    Max. Conductor Temp. (Normal Continuous)

    Max. Conductor Temp. (Overload)

    Max. Conductor Temp. (Short Circuit)

    260-EPR-01 1 Solid 13 14 0.289 Inches 0.870 Inches 0.950 Inches 1.078 Inches 1.178 Inches 657 Lbs 735 Lbs 195 Amps 145 Amps 127 Amps Aluminum 90 oC 130 oC 250 oC
    260-EPR-02 1 19 13 14 0.330 Inches 0.910 Inches 0.970 Inches 1.100 Inches 1.200 Inches 676 Lbs 757 Lbs 195 Amps 145 Amps 127 Amps Aluminum 90 oC 130 oC 250 oC
    260-EPR-03 1/0 Solid 16 14 0.325 Inches 0.905 Inches 0.989 Inches 1.117 Inches 1.217 Inches 736 Lbs 815 Lbs 220 Amps 165 Amps 145 Amps Aluminum 90 oC 130 oC 250 oC
    260-EPR-04 1/0 19 16 14 0.370 Inches 0.950 Inches 1.010 Inches 1.140 Inches 1.240 Inches 762 Lbs 845 Lbs 220 Amps 165 Amps 145 Amps Aluminum 90 oC 130 oC 250 oC
    260-EPR-05 2/0 19 13 12 0.420 Inches 0.990 Inches 1.060 Inches 1.190 Inches 1.290 Inches 886 Lbs 986 Lbs 250 Amps 190 Amps 167 Amps Aluminum 90 oC 130 oC 250 oC
    260-EPR-06 3/0 19 16 12 0.470 Inches 1.040 Inches 1.150 Inches 1.310 Inches 1.410 Inches 1038 Lbs 1141 Lbs 290 Amps 210 Amps 185 Amps Aluminum 90 oC 130 oC 250 oC
    260-EPR-07 4/0 19 20 12 0.530 Inches 1.100 Inches 1.210 Inches 1.370 Inches 1.470 Inches 1233 Lbs 1340 Lbs 325 Amps 245 Amps 215 Amps Aluminum 90 oC 130 oC 250 oC
      Results 1 - 7 of 7 1