American Wire Group - 345 MIL EPR 35 KV URD Cable<br>One Third Neutral<br>Copper Conductor
 Search Catalog
      GO   
 All Categories    345 MIL EPR 35 KV URD Cable
One Third Neutral
Copper Conductor
AWG CODE NAME FINDER
Enter code name in the search field to the left for specific product information
All Categories > 
Primary URD Cable
15KV-35KV
 > 345 MIL EPR 35 KV URD Cable
100% Insulation Level
 > 345 MIL EPR 35 KV URD Cable
One Third Neutral
Copper Conductor
 > View Items 

    Download PDF Download PDF     Email Email This Page     Save To Favorites Save To Favorites

345 MIL EPR 35 KV URD Cable
One Third Neutral
Copper Conductor

Check up to five results to perform an action.

URD Cable

larger image

Applications
For use on single phase and three phase primary underground distribution systems operating at 35kV phase to phase at 100% insulation level.  Suitable for either direct burial or installation in ducts.

Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.

Standards
  • Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
  • Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
  • Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.





  • Request InformationCompare Items   Results per Page : 
      Results 1 - 9 of 9 1 

    Item #

    Conductor Size AWG

    Conductor Stranding

    Copper Neutral No. of Wires

    Copper Neutral Size AWG

    Diameters Conductor

    Diameter Over Insulation

    Diameter Over Insulation Shield

    Diameter Over Neutral Wires

    Diameter Over Embedded Jacket

    Total w/o Jacket Weight

    Total w/ Embedded Jacket Weight

    Ampacity 3/C Direct Buried

    Ampacity 3/C Triplex Buried

    Ampacity 3/C Duct In Air

    Conductor
    Type

    Max. Conductor Temp. (Normal Continuous)

    Max. Conductor Temp. (Overload)

    Max. Conductor Temp. (Short Circuit)

    345-EPR-20 1/0 19 9 14 0.370 Inches 1.120 Inches 1.230 Inches 1.350 Inches 1.460 Inches 1102 Lbs 1221 Lbs 270 Amps 215 Amps 189 Amps Copper 90 oC 130 oC 250 oC
    345-EPR-21 2/0 19 11 14 0.420 Inches 1.170 Inches 1.270 Inches 1.400 Inches 1.500 Inches 1264 Lbs 1384 Lbs 305 Amps 240 Amps 211 Amps Copper 90 oC 130 oC 250 oC
    345-EPR-22 3/0 19 14 14 0.470 Inches 1.220 Inches 1.320 Inches 1.480 Inches 1.590 Inches 1444 Lbs 1569 Lbs 340 Amps 280 Amps 246 Amps Copper 90 oC 130 oC 250 oC
    345-EPR-23 4/0 19 11 12 0.530 Inches 1.280 Inches 1.380 Inches 1.540 Inches 1.710 Inches 1691 Lbs 1874 Lbs 380 Amps 315 Amps 276 Amps Copper 90 oC 130 oC 250 oC
    345-EPR-24 250 37 13 12 0.570 Inches 1.330 Inches 1.440 Inches 1.640 Inches 1.810 Inches 1939 Lbs 2133 Lbs 405 Amps 340 Amps 298 Amps Copper 90 oC 130 oC 250 oC
    345-EPR-25 350 37 12 10 0.680 Inches 1.440 Inches 1.540 Inches 1.700 Inches 1.890 Inches 2469 Lbs 2679 Lbs 460 Amps 400 Amps 350 Amps Copper 90 oC 130 oC 250 oC
    345-EPR-26 500 37 17 10 0.810 Inches 1.570 Inches 1.720 Inches 1.880 Inches 2.040 Inches 3273 Lbs 3533 Lbs 520 Amps 470 Amps 412 Amps Copper 90 oC 130 oC 250 oC
    345-EPR-27 750 61 25 10 0.990 Inches 1.760 Inches 1.930 Inches 2.110 Inches 2.280 Inches 4504 Lbs 4776 Lbs 567 Amps 550 Amps 483 Amps Copper 90 oC 130 oC 250 oC
    345-EPR-28 1000 61 33 10 1.140 Inches 1.920 Inches 2.060 Inches 2.270 Inches 2.430 Inches 5647 Lbs 5647 Lbs 625 Amps 615 Amps 540 Amps Copper 90 oC 130 oC 250 oC