American Wire Group - 345 MIL EPR 35 KV URD Cable
One Third Neutral
Aluminum Conductor
Search Catalog
By Keyword
By Item #
All Categories
345 MIL EPR 35 KV URD Cable
One Third Neutral
Aluminum Conductor
AWG CODE NAME FINDER
Enter code name in the search field to the left for specific product information
All Categories
>
Primary URD Cable
15KV-35KV
>
345 MIL EPR 35 KV URD Cable
100% Insulation Level
>
345 MIL EPR 35 KV URD Cable
One Third Neutral
Aluminum Conductor
>
View Items
Download PDF
Email This Page
Save To Favorites
345 MIL EPR 35 KV URD Cable
One Third Neutral
Aluminum Conductor
Check up to five results to perform an action.
larger image
Applications
For use on single phase and three phase primary underground distribution systems operating at 35kV phase to phase at 100% insulation level. Suitable for either direct burial or installation in ducts.
Construction
Copper or aluminum concentrically stranded compressed conductor, triple single head extruded conductor shield, EPR (ethylene propylene rubber) insulation and easy strippable insulation shield, all dry nitrogen cured; solid bare copper wires uniformly spaced around the cable as a concentric neutral; LLDPE jacket with extruded longitudinal colored stripes, surface printed.
Standards
Conforms to ICEA S-94-649 Std. for Concentric Neutral Cables Rated 5,000 - 46,000 V.
Conforms to ICEA S-97-682 Std. for Utility Shielded Power Cables Rated 5,000 - 46,000 V.
Conforms to AEIC CS8 Specification for Extruded Dielectric Shielded Power Cables Rated 5 through 46kV.
Results per Page :
25
50
100
200
Results 1 - 10 of 10
1
Item #
Conductor Size AWG
Conductor Stranding
Copper Neutral No. of Wires
Copper Neutral Size AWG
Diameters Conductor
Diameter Over Insulation
Diameter Over Insulation Shield
Diameter Over Neutral Wires
Diameter Over Embedded Jacket
Total w/o Jacket Weight
Total w/ Embedded Jacket Weight
Ampacity 3/C Direct Buried
Ampacity 3/C Triplex Buried
Ampacity 3/C Duct In Air
Conductor
Type
Max. Conductor Temp. (Normal Continuous)
Max. Conductor Temp. (Overload)
Max. Conductor Temp. (Short Circuit)
345-EPR-06
1/0
Solid
6
14
0.325 Inches
1.075 Inches
1.195 Inches
1.323 Inches
1.423 Inches
736 Lbs
815 Lbs
215 Amps
165 Amps
145 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-07
1/0
19
6
14
0.370 Inches
1.120 Inches
1.230 Inches
1.350 Inches
1.460 Inches
835 Lbs
935 Lbs
215 Amps
165 Amps
145 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-08
2/0
19
7
14
0.420 Inches
1.170 Inches
1.270 Inches
1.400 Inches
1.500 Inches
925 Lbs
1044 Lbs
245 Amps
190 Amps
167 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-09
3/0
19
9
14
0.470 Inches
1.220 Inches
1.320 Inches
1.480 Inches
1.590 Inches
1018 Lbs
1138 Lbs
275 Amps
215 Amps
189 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-10
4/0
19
11
14
0.530 Inches
1.280 Inches
1.380 Inches
1.540 Inches
1.710 Inches
1161 Lbs
1286 Lbs
305 Amps
245 Amps
215 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-11
250
37
13
14
0.570 Inches
1.330 Inches
1.440 Inches
1.640 Inches
1.810 Inches
1301 Lbs
1484 Lbs
335 Amps
270 Amps
238 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-12
350
37
11
12
0.680 Inches
1.440 Inches
1.540 Inches
1.700 Inches
1.890 Inches
1558 Lbs
1752 Lbs
390 Amps
320 Amps
280 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-13
500
37
16
12
0.810 Inches
1.570 Inches
1.720 Inches
1.880 Inches
2.040 Inches
2003 Lbs
2213 Lbs
440 Amps
385 Amps
338 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-14
750
61
15
10
0.990 Inches
1.760 Inches
1.930 Inches
2.110 Inches
2.280 Inches
2590 Lbs
2850 Lbs
515 Amps
475 Amps
417 Amps
Aluminum
90
o
C
130
o
C
250
o
C
345-EPR-15
1000
61
20
10
1.140 Inches
1.920 Inches
2.060 Inches
2.270 Inches
2.430 Inches
3143 Lbs
3415 Lbs
570 Amps
535 Amps
470 Amps
Aluminum
90
o
C
130
o
C
250
o
C
Results 1 - 10 of 10